SF6-free RMUs | BGS-12
Medium voltage ring main units for 12kV applications
BGS-12 stands for Brunstock Gas insulated Secondary switchgear, rated up to 12kV. This ring main unit utilises vacuum switching and SF6-free sealing technology. The main circuit and high-voltage components are sealed in the gas tank, making it suitable for operation under harsh environmental conditions, such as dust, humidity, saline air and even at high altitude.
This ring main unit is just 450mm x 800mm, a compact footprint that makes it a flexible solution which can be widely applied. You will find it in all kinds of kiosks in renewable wind/solar farms, in utility applications, and in airports and railways.

Application
BGS-12 is one of our SF6-free gas insulated switchgear series, which paves the way for you to enjoy a cleaner, greener footprint in your power transformation, distribution, storage and utilisation projects.
Our ring main unit packages are designed for the renewables, utilities, infrastructure, oil and gas, and mining industries with power transformation and distribution solutions to suit their project timeframes and budgets. We focus on a variety of industries by using our deep understanding of power engineering and manufacturing to offer world-class renewable energy products.

Why choose dry air to insulate your switchgear
Better for the planet than SF6
Using compressed dry air instead of SF6 (sulfur hexafluoride) in secondary switchgear ring main units offers several key benefits. Dry air is an environmentally friendly alternative because it is a natural and non-toxic gas with a significantly lower global warming potential compared to SF6, which has a much higher greenhouse effect. Additionally, dry air is less expensive and more readily available than SF6, making it a cost-effective choice for many applications. It also avoids the challenges associated with handling and disposing of SF6, which requires special protocols due to its high potency as a greenhouse gas.
In terms of performance, Brunstock’s dry air technology provides adequate insulation and arc extinguishing properties, thereby supporting the reliable and efficient operation of switchgear systems.
Better for your project budget
Using dry air instead of nitrogen (N2) in secondary switchgear can offer several distinct advantages. Firstly, dry air, being a mixture of nitrogen and oxygen, provides a more natural and stable insulating medium that can effectively support high-voltage applications while being less prone to issues related to partial discharge and dielectric breakdown compared to pure nitrogen.
Additionally, dry air is more readily available and often less expensive than pure nitrogen, which can lead to cost savings in terms of both procurement and system operation. Moreover, dry air, when properly conditioned to maintain low humidity, helps prevent the formation of condensation and corrosion within switchgear components, enhancing the overall reliability and lifespan of the Brunstock equipment.
Using dry air also avoids the need for the specialised handling and storage protocols required for high-purity nitrogen, simplifying maintenance and operational procedures.
It won’t cost more
Brunstock is offering SF6-free equipment that equates to or undercuts the SF6 competition. Can’t believe it, until you see it? Get in contact with your Brunstock rep to find out more.
About Brunstock
As an innovator in the energy industry, Brunstock represents environmentally friendly electric power system technologies. Led by a team of global power grid experts, Brunstock brings new technology to the world’s energy systems. Our range includes innovative green substation products: ester oil transformers, SF6-free RMUs and SF6-free primary GIS.


Benefits of BGS-12
- Environmentally friendly
- Cost efficient
- Maintenance free
- Safe and reliable
- Compact
- Operation continuity
- Fast delivery
Features
- Type tested according to IEC62271-100, IEC62271-200
- Metal enclosed, partition class PM
- Loss of service continuity category: LSC2B
- Protection index: Gas tank IP67, enclosure
- IP4X
- Mechanical endurance: circuit breaker 10,000 (M2), three-position disconnector/earthing switch 3000 (M1)



BGS-12 ring main unit technical data
Type | Measure | Description |
---|---|---|
Rated voltage | kV | 12 |
Rated main busbar current | A | 630 |
Rated circuit breaker current | A | 630 |
Power frequency withstand voltage | kV (1 min) | 42 |
Lightning impulse voltage | kV peak | 95 |
Short-time withstand current | kA/s | 20/3 |
Peak withstand current (50Hz) | kA | 50 |
Rated filling pressure at 20°C | MPa | 0.32 |
Gas leakage | %/year | ≤0.01 |
Rated operating sequence | | O-0.3s-CO-180s-CO |
Internal arc classifcation | kA/s | AFLR 20/1 |
Partial discharge (interval) | pC | ≤20 |
Environmental conditions this ring main unit can withstand
Type | Measure | Description |
---|---|---|
Ambient temperature | °C | -25 to +40 * |
Altitude | m | ≤2,000 above sea level * |
Relative humidity | % | Daily average ≤98 |
* Note: for further ambient temperature range or higher altitude, please consult your Brunstock representative.
Dimensions
Width | 450mm |
Depth | 800mm |
Height | 2250mm |
12 kV secondary SF6-free RMU
